Abstract
A computer simulation of combined and cogeneration gas turbine (GT) cycles with inlet air cooling has been conducted. The results indicate that for a simple gas turbine (203 MW ISO rating) with evaporative or fogging inlet air cooling the efficiency is around 50%. The calculated efficiency of the cogeneration cycle with inlet air cooling using absorption or vapour compression refrigeration is around 56% while that for the combined cycle with inlet air cooling (absorption or vapour compression refrigeration) is around 60%.